What is an EICR?
An Electrical Installation Condition Report (EICR) is a formal inspection of the fixed electrical wiring and installations in a property. It covers everything from the consumer unit (fuse box) to the sockets, light fittings, and any hard-wired appliances. It does not cover portable appliances like kettles or lamps — that is a separate PAT test.
The inspection is carried out by a qualified electrician or electrical contractor who will test the circuits, check for deterioration or damage, and identify anything that does not meet current safety standards.
Since 1 July 2020, having a valid EICR has been a legal requirement for all privately rented properties in England.
The legal requirements
The Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020 require landlords to:
- Have the electrical installations in their property inspected and tested at least every 5 years by a qualified person
- Ensure the first inspection is done before new tenants move in
- Provide a copy of the report to tenants within 28 days of the inspection
- Provide a copy to the local authority within 7 days if requested
- Provide a copy to prospective tenants within 28 days of receiving a request
- Complete any remedial work within 28 days (or sooner for urgent issues) if the report identifies problems
Who counts as a qualified person?
The electrician must be qualified and competent to carry out the inspection. In practice, this means they should be registered with one of the government-approved competent person schemes:
- NICEIC (National Inspection Council for Electrical Installation Contracting)
- NAPIT (National Association of Professional Inspectors and Testers)
- ELECSA
- BRE (Building Research Establishment)
- STROMA
Always ask to see the electrician's registration before they start work. An EICR from an unregistered person may not be accepted by your local authority.
What the inspection covers
During an EICR inspection, the electrician will:
- 1Visually inspect the electrical installation, checking for obvious defects, wear, and damage
- 2Test the circuits to check they are safe and working correctly
- 3Check the consumer unit (fuse box) to ensure it meets current standards
- 4Test RCDs (residual current devices) to confirm they trip correctly and protect against electric shock
- 5Check earthing and bonding to make sure the installation is properly earthed
- 6Identify any non-compliance with the current edition of the Wiring Regulations (BS 7671)
The inspection typically takes 2-4 hours for a standard property, depending on the size and number of circuits. For larger properties or HMOs, it can take longer.
The coding system
The report uses a coding system to classify any issues found:
- C1 (Danger present): An immediate risk to safety. The electrician should make the circuit safe before leaving. Remedial work is urgent.
- C2 (Potentially dangerous): Not immediately dangerous but could become so. Must be fixed within 28 days.
- C3 (Improvement recommended): Not a safety risk but does not meet the latest standards. No legal obligation to fix, but recommended.
- FI (Further investigation): The electrician cannot fully assess without further work. Must be investigated and resolved.
A report with only C3 observations is considered satisfactory. A report with any C1, C2, or FI codes is unsatisfactory and remedial work is required.
What happens if the EICR is unsatisfactory
If the report identifies C1, C2, or FI issues:
- 1You must complete the necessary remedial work within 28 days of the report (or sooner for C1 issues, which should be made safe immediately)
- 2You must have the work verified by a qualified person who provides written confirmation
- 3You must provide this written confirmation to your tenant within 28 days
- 4You must provide the confirmation to the local authority within 28 days if they have requested the original report
If you fail to complete the remedial work, the local authority can:
- Arrange for the work to be done themselves and charge you for it
- Issue a remedial notice requiring you to complete the work
- Take the matter to the First-tier Tribunal
Penalties for non-compliance
The penalties for failing to meet EICR requirements are severe:
- Financial penalty: Up to £30,000 per breach, issued by the local authority
- Remedial action costs: If the council arranges the work, you pay for it plus their administrative costs
- Section 21 restrictions: You cannot serve a valid Section 21 notice until you have provided the EICR report to your tenant
- Rent repayment orders: If a financial penalty is issued, tenants can apply for a rent repayment order of up to 12 months' rent
The £30,000 figure is not theoretical. Local authorities have been actively enforcing these regulations since 2020, and fines of £10,000-£20,000 are not uncommon for landlords who fail to comply.
How much does an EICR cost?
Typical costs for an EICR in 2026:
| Property type | Typical cost |
|---|---|
| 1-bed flat | £120 - £180 |
| 2-3 bed house | £150 - £250 |
| 4-5 bed house | £200 - £350 |
| HMO (6+ rooms) | £300 - £500+ |
These prices are for the inspection only. If remedial work is needed, that is charged separately and the cost depends on what needs to be fixed. Simple issues like replacing a faulty socket might cost £50-£100. Major work like upgrading a consumer unit can cost £500-£1,000+.
Always get quotes from multiple electricians and check they are registered with an approved competent person scheme.
Common issues found during EICR inspections
The most frequent problems electricians find during rental property inspections:
- Old consumer units without RCD protection: Properties with older fuse boxes often lack RCD protection, which is now a standard safety requirement. Upgrading the consumer unit is the most common (and most expensive) remedial action.
- Lack of earthing or bonding: Older properties may have inadequate earthing, especially in kitchens and bathrooms. This is a safety risk and typically coded C1 or C2.
- Damaged or deteriorated wiring: Particularly in older properties where the original wiring may be 30-40+ years old. If the wiring is very old (rubber-insulated or lead-sheathed), a full rewire may be recommended.
- Overloaded circuits: Extensions and modifications over the years can leave circuits carrying more load than they were designed for.
- Missing or broken socket covers: A minor issue but often flagged.
EICR for HMOs
Houses in Multiple Occupation (HMOs) have additional electrical safety requirements:
- The EICR requirement applies to all HMOs, not just those that require a licence
- HMOs must meet the fire safety requirements for electrical installations, including adequate fire detection and alarm systems
- The local authority may impose additional conditions through the HMO licence relating to electrical safety
- Fire doors must not be held open with electrical devices unless they are connected to an approved automatic fire detection system
If you manage HMOs, it is worth having the electrician check the property against both the EICR requirements and any specific conditions in your HMO licence.
Tracking your EICR expiry dates
Unlike gas safety certificates which renew annually, EICRs are valid for 5 years. This longer interval makes them easier to forget about. A certificate that was done in 2021 expires in 2026 — and if you manage multiple properties acquired at different times, each one has a different expiry date.
Most landlords and letting agents track compliance dates in one of three ways:
- Manually: Calendar reminders or a note in a filing system. Unreliable at scale but workable for one or two properties.
- Spreadsheets: A step up from calendar reminders, but nobody sends you an alert when a date is approaching. You have to remember to check.
- Compliance tracking software: Purpose-built tools like Proplio track all your certificate types — EICR, gas safety, EPC, and more — across every property in your portfolio. The dashboard shows you at a glance which properties are compliant, which have certificates expiring soon, and which are overdue. Automatic email reminders go out at 90, 60, 30, 14, and 7 days before any certificate expires.
With a potential £30,000 fine for non-compliance, having a reliable tracking system is not optional — it is a cost of doing business as a landlord.
Key takeaways
- A valid EICR has been legally required for all privately rented properties in England since July 2020
- Inspections must be done at least every 5 years by a qualified, registered electrician
- Unsatisfactory reports require remedial work within 28 days
- Fines for non-compliance go up to £30,000 per breach
- You cannot serve a valid Section 21 notice without providing the EICR to your tenant
- The 5-year interval makes it easy to forget — set up reminders well in advance
This article is for general guidance and applies to England. The Electrical Safety Standards regulations apply to England only — Scotland, Wales, and Northern Ireland have different requirements. Always check current requirements with your local authority or a qualified adviser.